4 zones conventional fire alarm security host control panel CK1004

4 zones conventional fire alarm security host control panel	CK1004

Model No.︰ck1004

Brand Name︰zc

Country of Origin︰China

Unit Price︰US $ 130 / pc

Minimum Order︰1 pc

Inquire Now

Product Description

Conventional Fire Alarm Control System :Conventional Fire Alarm Control Panel
 



 

General

Conventional Fire Alarm Control Panel with four Zones

Key Specifications/Special Features

  • Four Style B (Class B) Initiating Device Circuits (IDCs).
  • All zones accept two-wire smoke detectors and any normally-open contact devices.
  • One built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
  • Alarm, Trouble and Supervisory, Form-C relays standard.
  • 24-volt operation.
  • Resettable four-wire smoke detector power @ 500 mA.
  • Non-resettable power @ 500 mA.
  • One-man walk-test programmable for silent or audible test.
  • Disable/Enable control per IDC.
  • Reverse polarity protection.

Specifications

 

AC Power

90-270 VAC, 50 Hz, 2.3 amps

Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation

Battery (lead acid only)

Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp

Maximum Charger Capacity: 18 Amp Hour batter

Sound Output Device Circuits

General Alarm Zones 1 through 16

Operation: All zones Class B

Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)

Alarm Current: 15 mA threshold

Short Circuit Current: 42 mA maximum

Maximum Loop Resistance: 100 ohms

End-of-Line Resistor: 4.7K, ½ watt

Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone

Standby Current: 7.26 mA

Three Relays Output

Relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)

Nonresettable 24 VDC Power

Maximum ripple voltage: 10 mVRMS          Operating Voltage nominal 24 volts

Total DC current available from this output is up to 500 mA

Recommended maximum Standby current is 150 mA

 

Payment Terms︰ T/T,WU,PAYPAL

Product Image