- TCMK5203 Addressable Single I/O Module
Used to connect with linkage devices of fire alarm control panel, such as exhaust valve, air valve, fire damper etc., and can receive action response signal from device
Non-polarized two-wire
Electronically addressed
Active output and passive output
The input terminal can be in field set to normally open detection wire or self-answer mode, which can be connected with passive contact
Technical Specifications
Operating voltage:
Loop: 24V (16V~28V)
Power: DC24V (DC20V~DC28V)
Standby current:
Loop: ≤0.2mA
Power: ≤2mA
Starting current:
Loop: ≤2mA
Power: ≤22mA
Operating Environment:
Temperature: -10°C~+55°C
Relative Humidity: ≤95%, non-condensing
Output capacity:
Passive output
Capacity: DC30V/3A
Contact resistance in normal condition: 100kΩ
Closed when activated
Suitable for DC or AC12V~48V
Active output
Capacity: DC24V/1.5A
Indicator: Red
Input indicator
Flashes when polling
Illuminates in action
Output indicator
Illuminates in action
Programming method: Electronically programming
Code range: One address is within 1~255
Material and color of enclosure: ABS; Porcelain white
Weight: About 147g (with base)
Mounting hole distance: 60mm
Dimension (L×W×H): 86mm×86mm×38mm (with base)